Still deciding? Get samples of $ !
Order Sample
|
| Customization: | Available |
|---|---|
| Output Type: | Single |
| Warranty: | 3 Years |
| Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
|---|
| Payment Methods: |
|
|---|---|
| Support payments in USD |
| Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
|---|
| Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
|---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
3 Years Warranty Full Range Input Voltage PSC-150-24 150W 27.6V 4A and 27.6V 1.5A(Charger) Ac to Dc Switching Power Supply
Features:
1. International universal AC input voltage range
2.Small size, light weight, high efficiency
3.Protection features: short circuit/overload
4.Battery low voltage protection
5.With power on/charging/mains power display (LED)
6.100% full load burn-in test
7.Power on LED indicator
8.3-year quality assurance
| Model | PSC-150-12 | PSC-150-24 | ||||
| Output | DC output voltage | CH1:13.8V | CH2:13.8V | CH1:27.6V | CH2:27.6V | |
| Output voltage tolerance | ±1% | ----- | ±1% | ----- | ||
| Rated output current | 7.5A | 3A(Charge) | 4A | 1.5A(Charge) | ||
| Output current range | 0~4.5A | ----- | 0~2.2A | ----- | ||
| Output Power | 150W | 152W | ||||
| Ripple and noise | 150mVp-p | ----- | 200mVp-p | ----- | ||
| DC voltage adjustable range | CH1:11.3~14.9V | CH1:21.3~29.8V | ||||
| Start, rise, hold time | 600ms,50ms,80ms/230VAC.1200ms,50ms,16ms/115VAC | |||||
| Input | Input voltage range | 90~264VAC or 135~370VDC | ||||
| AC input current | 3.2A/115VAC 1.6A/230VAC | |||||
| efficiency | 86% | 88% | ||||
| Inrush current | Cold starting current30A/115VAC 50A/230VAC | |||||
| Leakage Current | <1mA/240VAC | |||||
| Protection Features |
Overload protection | Rated output power105%~115%Start overload protection | ||||
| Protection mode: AC charging mode: Isolation mode, automatic recovery after abnormal load conditions are removed; | ||||||
| Battery low voltage protection | 9.5~10.3V | 19~20.5V | ||||
| Protection mode: cut off the output, | ||||||
| Function | UPS Function Introduction | Long-term online floating charging of the battery has high charging efficiency and the battery fullness can be as high as over 97%. | ||||
| Automatically stops when fully charged to prevent overcharging of the battery, effectively extending the battery life | ||||||
| Automatic switching between AC power and battery, no switching time, no need for human supervision. | ||||||
| Cold start function: when there is no mains power, the UPS can be started directly with the battery to meet the user's emergency needs | ||||||
| environment | Working temperature, humidity | -20ºC~+60ºC;20%~90%RH(Please refer to the load derating curve) | ||||
| Storage temperature and humidity | -20ºC~+85ºC;10%~95%RH No condensation | |||||
| Shock resistance | 10~500Hz, 2G 10min./1 cycle, duration 60 minutes, each axis | |||||
| Safety | Pressure resistance | Between input and output: 1.5KVAC Input and ground: 1.5KVAC Output and ground: 0.5KVDC | ||||
| Insulation resistance | Between input and output: input and ground, output and ground: 100M Ohms/500VDC | |||||
| Other | size | 159*97*30mm(L*W*H) | ||||
| Package | 0.55Kg/30pcs/18.5kg/0.041 cubic meter | |||||
| Remark | 1. All parameters are measured at 230VAC input voltage, rated load and 25ºC unless otherwise specified. 2. Ripple and noise voltage are measured with a 20MHz bandwidth oscilloscope with 0.1μ and 47μ capacitors added to the end of a 12-inch twisted pair. 3. Tolerance is the sum of voltage setting error, voltage regulation and current regulation. |
|||||