Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 5 Years |
Still deciding? Get samples of US$ 185/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL | RSP-1000-12 | RSP-1000-15 | RSP-1000-24 | RSP-1000-27 | RSP-1000-48 | |||
OUTPUT | DC VOLTAGE | 12V | 15V | 24V | 27V | 48V | ||
RATED CURRENT | 60A | 50A | 40A | 37A | 21A | |||
CURRENT RANGE | 0~60A | 0~50A | 0~40A | 0~37A | 0~21A | |||
RATED POWER | 720W | 750W | 960W | 999W | 1008W | |||
RIPPLE &NOISE(max.)Note.2 | 150mVp-p | 150mVp-p | 150mVp-p | 150mVp-p | 150mVp-p | |||
VOLTAGE ADJ.RANGE | 10~13.5V | 13.5~16.5V | 20~26.4V | 24~30V | 43~55V | |||
VOLTAGE TOLERANCE Note.3 | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |||
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | |||
LOAD REGULATION | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | |||
SETUP,RISE TIME | 300ms,50ms at full load | |||||||
HOLD UPTIME(Typ.) | 16ms/230VAC 16ms/115VAC at full load | |||||||
INPUT | VOLTAGE RANGE Note.4 | 90~264VAC 127~370VDC | ||||||
FREQUENCY RANGE | 47~63Hz | |||||||
POWER FACTOR(Typ.) | 0.95/230VAC 0.98/115VAC at full load | |||||||
EFFICIENCY(Typ.) | 83% | 85% | 88% | 88% | 90% | |||
AC CURRENT (Typ.) | 12A/115VAC 6A/230VAC | |||||||
INRUSH CURRENT(Typ.) | 25A/115VAC 40A/230VAC | |||||||
LEAKAGECURRENT | <2.0mA/240VAC | |||||||
PROTECTION | OVERLOAD | 105~125%rated output power | ||||||
Protection type:Constant current limiting,recovers automatically after fault condition is removed | ||||||||
OVER VOLTAGE | 13.8~16.8V | 17~20.5V | 27.6~32.4V | 31~36.5V | 56.6~66.2V | |||
Protection type:Shut down o/p voltage,re-power on to recover | ||||||||
OVERTEMPERATURE | Shut down o/p voltage,recovers automatically aftertemperature goes down | |||||||
FUNCTION | 0UTPUT VOLTAGE PROGRAMMABLE/PV) | Adjustment of output voltageis allowable to 40~110%of nominaloutput voltage.Please refer to the Function Manual. | ||||||
CURRENT SHARING | Up to 4000W or(3+1)units.Please refer to the Function Manual. | |||||||
AUXILIARY POWER | [email protected](+5%,-8%) | |||||||
REMOTE ON-OFF CONTROL | Power ON:short Power OFF:open.Please refer to the Function Manual. | |||||||
REMOTE SENSE | Compensate voltage drop on the load wiring up to 0.5V.Please refer to the Function Manual. | |||||||
DC OK SIGNAL | The TTL signal out,PSU tum on=0~1V;PSU turn off=3.3~5.6V.Please refer to the Function Manual. | |||||||
ENVIRONMENT | WORKING TEMP. | -20~+60ºC(Refer to "Derating Curve") | ||||||
WORKING HUMIDITY | 20~90%RH non-condensing | |||||||
STORAGE TEMP,HUMIDITY | -40~+85ºC,10~95%RH non-condensing | |||||||
TEMP.COEFFICIENT | ±0.02%/ºC(0~50ºC) | |||||||
VIBRATION | 10~500Hz,2G 10min./1cycle,60min.eachalongX,Y,Z axes | |||||||
SAFETY& EMC (Note 5) |
SAFETY STANDARDS | UL62368-1,CSAC22.2 No.62368-1,TUVBS EN/EN62368-1,CCC GB4943.1,BSMI CNS14336-1,AS/NZS62368.1, IS13252(Part1)IEC60950-1,EAC TP TC 004 approved |
||||||
WITHSTANDVOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | |||||||
ISOLATION RESISTANCE | I/P-O/P,I/P-FG,O/P-FG:100M Ohms/500VDC125ºC170%RH | |||||||
EMC EMISSION | Parameter | Standard | Test Level/Note | |||||
Conducted | BS EN/EN55032(CISPR32) | Class B | ||||||
Radiated | BS EN/EN55032(CISPR32) | ClassA | ||||||
Harmonic Current | BS EN/EN61000-3-2 | |||||||
Voltage Flicker | BS EN/EN61000-3-3 | |||||||
EMC IMMUNITY | BS EN/EN55035,BS EN/EN61000-6-2,CCC GB17625.1,GB/T9254,BSMI CNS13438 | |||||||
Parameter | Standard | Test Level/Note | ||||||
ESD | BS EN/EN61000-4-2 | Level 3,8KVair;Level2,4KV contact | ||||||
Radiated | BS EN/EN61000-4-3 | Level 3 | ||||||
EFT/Burst | BS EN/EN61000-4-4 | Level 3 | ||||||
Surge | BS EN/EN61000-4-5 | Level 4,4KV/Line-Earth;Level3,2KV/Line-Line | ||||||
Conducted | BS EN/EN61000-4-6 | Level 3 | ||||||
Magnetic Field | BS EN/EN61000-4-8 | Level 4 | ||||||
Voltage Dips and Interruptions | BS EN/EN61000-4-11 | >95%dip 0.5 periods,30%dip25 peniods, >95%interruptions 250 periods |
||||||
OTHERS | MTBF | 939.4Khrs min.Telcordia SR-332(Bellcore);116.5K hrs min.MIL-HDBK-217F(25ºC) | ||||||
DIMENSION | 295*127*41mm(L*W*H) | |||||||
PACKING | 1.95Kg;6pcs/12.7Kg/1.15CUFT | |||||||
NOTE |
1.All parameters NOT specially mentioned are measured at 230VAC input,rated load and 25ºC of ambient temperature. 2.Ripple &noise are measuredat 20MHz of bandwidth by using a 12"twisted pair-wire teminated with a 0.1uf &47uf parall capacitor. 3.Tolerance :includes set up tolerance,line regulation and load regulaton. 4.Derating may be needed under low input voltages.Please check the derating curve for more details. 5.The power suply is considereda component which wil be instaled into a find equipment AIl the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of hickness.The fial equipment must be re-confirmed that itsill meets EMC drectves.For guidance on how to perfom these EMC tests,please refer to"EMI testing of component power supplies. " (asavailable on Upload/PDF/EMI_statement_en.pdf) 6.The ambient temperaturederating of 3.5ºC/1000m with fanless models and of 5ºC1000m with fan models for operating altude higherthan 2000m(6500) |