Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 5 Years |
Still deciding? Get samples of US$ 1437.12/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment methods: | |
---|---|
Support payment in USD |
Secure payments: | Every payment you make at Made-in-china.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Mean Well RST-7K5-HV 115V 65A 230V 32.4A 380V 19.77A High power Three-phase input Water cooling or forced air cooling optional 5-year warranty
MODEL | RST-7K5-115 | RST-7K5-230 | RST-7K5-380 | |
OUTPUT | DC VOLTAGE (factory default) | 115V | 230V | 380V |
CURRENT (factory default) | 65A | 32.4A | 19.77A | |
CURRENT RANGE | 0~65A | 0~34.5A | 0-22.5A | |
RATED POWER | 7475W | 7452W | 7515W | |
FULL POWER VOLTAGE RANGE | 115-138V | 216~260V | 334~400V | |
RIPPLE &NOISE(max.)Note.2 | 1Vp-p | 2Vp-p | 4Vp-p | |
VOLTAGE ADJ.RANGE | 90~138V | 170-260V | 260~400V | |
Can be adjusted via built-in potentiometer | ||||
VOLTAGE TOLERANCE Note.3 | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±0.5% | ±0.5% | ±0.5% | |
SETUP,RISETIME | 3000ms,200ms at full oad | |||
HOLDUP TIME(Typ) | 16ms 230VAC/400VACat 75%load 10ms/230VAC/400VAC atfull load | |||
INPUT | VOLTAGE RANGE | 3y3W/△196-305VACor3y4WY 340-530VAC | ||
FREQUENCY RANGE | 47-63Hz | |||
POWER FACTOR(Typ.) | ≥0.98/230VAC(400VAC)/≥0.97/277VAC(480VAC)at full load | |||
EFFICIENCY (Typ.) Note.7 | 94% 95% 95% | |||
AC CURRENT(Typ-) | 22.5A230VAC(343-wrel△) 13A/400VAC344-wire/Y) | |||
INRUSH CURRENT(Typ.) | 75A/230VAC(3φ3-wire I△) 50A/400VAC(344-wire/Y) | |||
LEAKAGE CURRENT | <3.5mAY530VAC <10mAI△305VAC | |||
PROTECTION | OVERLOAD | 100-107%of ratedcurent | ||
Protection type:Constant current limiting,unit will shutdownafter5 sec.re-power on to recover | ||||
OVERVOLTAGE | 145-166V 273~312V 420-480V | |||
Protection type:Shut down olp voltage,re-power on to reoover | ||||
OVERTEMPERATURE | Shut downolpvoltage,recovers automatically after temperaturegoes down | |||
FUNCTION | CURRENT SHARING | Up to 4units.Please refer to the Function Manual | ||
0UTPUTVOLTAGE PROGRAMMABLE | Adjustment of output woltage is alowable between1~120%of nominaloutput voltage.Pleaserefer to the PVcurve Function Manual | |||
CONSTATCURBNT EVEL PR0GRAMMABLE | Adjustmentof constant current level is allowablebetween 20~100%of rated cument.Pleaserefer to the Function Manual | |||
REMOTE ON-OFF CONTROL | Please refer tothe FunctionManual | |||
ALARMSIGNALOUTPUT | AC fail,DCOK,fan fail,OTP.Please refer to the Function Manual | |||
ENMIROMENT | WORKING TEMP | -30~+70ºC (Referto "Derating Curve") | ||
WORKING HUMIDITY | 20-90%RH non-condensing | |||
STORAGE TEMP,HUMIDITY | -40~+85ºC,10~95%RH non-condensing | |||
TEMP.COEFFICIENT | ±0.03%/C (0~45ºC) | |||
VIBRATION | 10~500Hz,2G 10min.AIcycle,60min.each along X,Y,Zaxes | |||
SAFETY& EMC (Note 8) |
SAFETY STANDARDS | UL62368-1,CANCSAC22.2 No.62368-1,TUVBS EN/EN62368-1,EAC TPTC 004approved | ||
WITHSTANDVOLTAGE Note.4 | VP-OIP:4.3KVDC VP-FG:2.8KVDC O/P-FG2.8KVDC | |||
SOLATION RESISTANCE Note.4 | MP-OIP,MP-FG,0/P-FG:100M Ohms/500VDC125ºC/70%RH | |||
EMC EMISSION | Parameter | Standard | Test Level/Note | |
Conducted | BS ENEM55032|CISPR32)/BS ENEN55011(CISPR11) | ClassA | ||
Radiated | BSENEN55032|CISPR32)/BS ENEN55011 (CSPR11) | ClassA | ||
Harmonic Current | BS ENEN61000-3-2 | |||
VoltageFlicker | BS ENEN61000-3-3 | |||
EMC IMMUNITY | BS EN/EN55024,BS EN/EN61204-3,BS ENEN61000-6-2 | |||
Parameter | Standard | Test Level/Note | ||
ESD | BS ENEN61000-4-2 | Level 3,8KV air;Level2,4KV oontact | ||
Radiated | BS ENEN61000-4-3 | Level 3 | ||
EFT/Burst | BS ENEN61000-4-4 | Level 3 | ||
Surge | BS ENEN61000-4-5 | Level4,4KVLine-Earth;Level 3,2KWLine-Line | ||
Conducted | BS ENEN61000-4-6 | Level 3 | ||
Magnetic Field | BS ENEN61000-4-8 | Level4 | ||
Voltage Dips and Interruptions | BS ENEN61000-4-11 | >95%dip 0.5periods,30%dip 25 periods >95%interruptions 250 periods |
||
OTHERS | MTBF | 234.5Khrs min.Telcordia SR-332(Bellcore);27.1Khrs min.MIL-HDBK-217F(25ºC) | ||
DIMENSION | RST-7K5:460*211*83.5mm(L*W*H) RST-7K5-L:460*216*83.5mm(L*W*H) | |||
PACKING | RST-7K5:12Kg;1pcs/13Kg/1.25CUFT RST-7K5-L:12Kg;1pcs/13Kg/1.05CUFT | |||
NOTE | 1.Al parameters NOT specaly mentioned are measured at △230VAC(Y 400VAC)input rated load and 25ºC of ambient temperature. 2.Fipple &noise are measured at 20MHz ofbandwidth byusing a 12"twisted pair-wire terminated with a 0.1uf &47uf paralel capacitor. 3.Toleranoe indudes set up tolerance,line regulation andload regulation. 4.Duing withstand volage and isolation resistance testing,the screw"A"shall be temporariy removed,and shallbe instaled back afer he testing 5.Derating may be needed under lowinputvoltages.Pleasecheck the derating curve for more details. 6.If use PVsgnal o adjustVo,under creatin operation conditions,ipple noise of Vo might go over ating defined in this specfication. 7.The effciencyis measuedat △:230VACM:400VACinput.The efioiengy levelis measuedat output wofage 115V(115V mode)230V(230V modey 380V(380V model) 8.The power supply is consdered a component which wil be instaled into a final equipment.Al the EMCtestsare been executedby mounting the unt on a600mm-900mm metal plate with 1mm of thickness.The fnal equjpment must be ie-confrmed that itstllmeets EMC drectves.For guidance on howto perfom theseEMC tests,please refer to EMI tosting of component power supplies. (asavailable on https/hwww.meanwellcom//Upload/PDFEMI_statement_en.pdf) 9.The ambient temperature derating of 3.5ºC1000m with fanless modes and of 5ºCN000m with fan models for operatng alitude higher than 2000m(6500m 10.An unsable OIP votage is expectedinthefirst 300ms afer poweron.A mnimum load of 5%is suggested ffast load changeis requred atpower on phase Product LiabityDiscain douooor390 |
Q1:Why choose us?
A1:Original MEANWELL brand 100% original real MEANWELL brand, and have UL, CUL, CE, CB, RoHS and other certificates. The product surface has different S/N codes, you can check the code with MEANWELL company.
Q2: Do you have any MOQ limit?
A2: No MOQ, for most models we have stock 1pcs also ok. If the model not commonly used, we will quote the price and MOQ.
Q3:What about the lead time?
A3:Delivery time about 3-7 days, mass production time depends on order quantity and model.
Q4:How do you ship the goods and how long does it takes?
A4:We usually ship via DHL, UPS, FedEx or TNT. It will takes about 3-7 days to arrive. Airline and sea shipping also optional.
Q5:Do you offer guarantee for the products?
A5:Off course, 2-7 years warranty.