Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 3 Years |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL | ICL-16R | ICL-16L | |||||
AC INPUTVOLTAGE | 180~264VAC | ||||||
ACLINE FREQUENCY | 47~63Hz | ||||||
INRUSH CURRENT LIMITING | 23A | ||||||
AC CONTINUOUS RATED CURRENT | 16A continuous | ||||||
AC INPUT POWER | 3680VA(16Ax230VAC) | ||||||
AC INPUT CONSUMPTION | <1.5W at 264VAC,50Hzinput | ||||||
INTERNALRELAYLIMITING TIME (TON POWER ON) |
300±50ms | ||||||
INTERNALRELAY | LIMITING CYCLES | PSU Setup time<250ms | PSU Set up time 250~350ms | PSU Set up time>350ms | |||
1 cycle/5min | 1 cycle/1 min | 5 cycle/1min(>1500ms per cycle) | |||||
RELEASE TIME | 500±50ms |
||||||
INTERNAL PROTECTION | Thermal fuse protects overload and fire | ||||||
ALLOWED CAPACITIVE LOAD | 2500μF max. | ||||||
WORKINGTEMP. | -30~+70ºC | ||||||
WORKING HUMIDITY | 20~90%RH non-condensing | ||||||
STORAGE TEMP. | -40~+85ºC |
||||||
TEMP.COEFFICIENT | ±0.03%/ºC (0~50ºC)RH non-condensing | ||||||
VIBRATION | 10~500Hz,2G 10min./1cycle,period for 60min.each along X,Y,Zaxes; | ||||||
Mounting:Compliance to IEC60068-2-6 | |||||||
OPERATING ALTITUDE (NOTE 2) | 5000 meters | ||||||
OVER VOLTAGE CATEGORY | ;According to IEC62368-1;altitude up to 5000 meters | ||||||
POLLUTION DEGREE | 2 | ||||||
SAFETY STANDARDS | LVD BS EN/EN62368-1 approved | ||||||
SAFETY& EMC (Note.3) |
EMC EMISSION | Parameter | Standard | Test Level/Note | |||
Conducted | BS EN/EN55032 | Class B | |||||
Radiated | BS EN/EN55032 | Class B | |||||
Harmonic Current | BS EN/EN61000-3-2 | ClassA | |||||
Voltage Flicker | BS EN/EN61000-3-3 | ------- |
|||||
EMC IMMUNITY | BS EN/EN55035,BS EN/EN61000-6-2 | ||||||
Parameter | Standard | Test Level/Note | |||||
ESD | BS EN/EN61000-4-2 | Level 3,8KV air;Level2,4KV contact,criteria A | |||||
Radiated Susceptibilit | BS EN/EN61000-4-3 | Level 3,criteriaA | |||||
FFT/Burest | BS EN/EN61000-4-4 | Level 3,criteriaA | |||||
Surge | BS EN/EN61000-4-5 | Level4,2KV/L-N,criteriaA | |||||
Conducted | BS EN/EN61000-4-6 | Level 3,criteria A | |||||
Magnetic Field | BSEN/EN61000-4-8 | Level 4,criteriaA | |||||
Voltage Dips and interruptions | BS EN/EN61000-4-11 | >95%dip 0.5 periods,30%dip 25 periods, >95%interruptions250 periods |
|||||
MTBF | 7229.0K hrs min.Telcordia SR-332(Bellcore); 2157.3K hrs min. MIL-HDBK-217F (25ºC) |
7217.9Khrs min.Telcordia SR-332 (Bellcore); 2113.8Khrs min. MIL-HDBK-217F (25ºC) |
|||||
DIMENSION | 35*90*54.5mm(L*W*H | 175*42*24mm(L*W*H) | |||||
PACKING | 0.116Kg;96pcs/12.2Kg/1.04CUFT | 0.132Kg;98pcs/14Kg/1.04CUFT | |||||
NOTE | 1.All parameters NOT specially mentioned are measured at 230VAC input,rated load and 25ºC of ambient temperature. 2.The ambient temperature derating of 3.5ºC/1000m with fanless models and of 5ºC/1000m with fan models for operating altitude higher than 2000m(6500ft). 3.The power supply is considered as an independent unit,but the final equipment still need to re-confim that the whole system complies with the EMC directives.For guidance on how to perform these EMC tests,please refer to"EMI testing of component power supplies. " |