Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 5 Years |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL | UHP-1500-380E | |||
OUTPUT | DC VOLTAGE(DEFAULT) | 380V | ||
RATED CURRENT(Max.) | 3.95A | |||
RATED POWER(Max.)(Note.7) | 1501W | |||
RIPPLE &NOISE(Max.)Note.2 | 3800mVp-p | |||
VOLTAGE ADJ.RANGE | By built-in potentiometer,SVR | |||
350~420V | ||||
VOLTAGE TOLERANCE Note.3 | ±1.0% | |||
LINE REGULATION | ±0.5% | |||
LOAD REGULATION | ±0.5% | |||
SETUP,RISE TIME | 1800ms,60ms/230VAC at full load | |||
HOLD UP TIME(Typ.) | 16ms/230VAC at75%load 10ms/230VAC at full load | |||
INPUT | VOLTAGE RANGE Note.4 | 90~264VAC 250~370VDC | ||
FREQUENCY RANGE | 47~63Hz | |||
POWER FACTOR(Typ.) | PF≥0.95/230VAC at full load | |||
EFFICIENCY(Typ.) | 95.5% | |||
AC CURRENT (Typ. | 8A/230VAC | |||
INRUSH CURRENT (Typ.) | Cold start 60A/230VAC | |||
LEAKAGE CURRENT | <0.75mA/240VAC | |||
PROTECTION | OVER LOAD | 105~125%rated output power | ||
Protection type:Constant current limiting,unit willshutdown after 2-5 sec,re-power on to recover. | ||||
SHORT CIRCUIT | Constant current limiting,unit will shutdown after 2-5 sec,re-power on to recover. | |||
OVER VOLTAGE | 428~460V | |||
Protection type :Shut down O/P voltage,re-power on to recover | ||||
OVER TEMPERATURE | Protection type :Shut down O/P voltage,recovers automatically after temperature goes down | |||
FUNCTION | REMOTE ON/OFF CONTROL | PowerON:Short circuit PowerOFF:Open circuit | ||
ENVIRONMENT | WORKING TEMP. | -30~+70ºC(Referto "Derating Curve") | ||
WORKING HUMIDITY | 20~90%RH non-condensing | |||
STORAGE TEMP.,HUMIDITY | -40~+85ºC,10~95%RH non-condensing | |||
TEMP.COEFFICIENT | ±0.03%/ºC(0~50ºC) | |||
VIBRATION | 10~500Hz,5G 10min.1cycle,60min.each along X,Y,Zaxes | |||
SAFETY & EMC (Note.6) |
SAFETY STANDARDS | UL62368-1,TUVBS EN/EN62368-1,EAC TP TC 004 approved | ||
WITHSTAND VOLTAGE Note 8 | OVC I/P-O/P:6KVDC I/P-FG:4KVDC O/P-FG:4KVDC | |||
ISOLATION RESISTANCE Note 8 | /P-O/P,I/P-FG,0/P-FG:100M Ohms/500VDC/25ºC/70%RH | |||
EMC EMISSION | Parameter | Standard | Test Level/Note | |
Conducted | BS EN/EN55032 (CISPR32) | Class B | ||
Radiated | BS EN/EN55032(CISPR32) | Class A | ||
Harmonic Current | BS EN/EN61000-3-2 | Class A | ||
Voltage Flicker | BS EN/EN61000-3-3 | |||
EMC IMMUNITY | BS EN/EN61000-6-2 | |||
Parameter | Standard | Test Level/Note | ||
ESD | BS EN/EN61000-4-2 | Level 3,8KVair;Level2,4KV contact | ||
Radiated | BS EN/EN61000-4-3 | Level 3 | ||
EFT/Burst | BS EN/EN61000-4-4 | Level 3 | ||
Surge | BS EN/EN61000-6-2 | 2KV/Line-Line 4KV/Line-Earth | ||
Conducted | BS EN/EN61000-4-6 | Level 3 | ||
Magnetic Field | BS EN/EN61000-4-8 | Level 4 | ||
Voltage Dips and Interruptions | BS EN/EN61000-4-11 | >95%dip 0.5 periods,30%dip 25periods, >95%interruptions 250 periods |
||
OTHERS | MTBF | 597.3K hrs min.Telcordia SR-332(Bellcore);63.3K hrs min.MIL-HDBK-217F (25ºC) | ||
DIMENSION | 290*140*41mm(L*W*H) | |||
PACKING | 2.51kg;6pcs/16.06kg/0.91CUFT | |||
NOTE | 1.All parameters NOT specily mentioned are measured at 230VAC input,rated load and 25ºC of ambient temperature. 2.Ripple &noise are measured at 20MHz of bandwidth by using a 12"twisted pair-wire terminated with a 0.1uf &47uf parllel capacitor. 3.Tolerance :includes set up tolerance,line regulation and load regulation. 4.Derating may be needed under low input voltages.Please check the derating curve for more details. 5.The power supply is considered a component which willbe insaled into a final equipment.A the EMC tests are been executed by mouning the unit on a720mm*360mm metal plate with Imm of hckness.The final equipment must be re-confirmed that it til meets EMC drectves.For guidance on how to perform these EMC tests,please refer to "EMI testing of component powersupplies. " 6.The ambient temperaturederating of 3.5ºC1000m with fanless modes and of 5C1000m with fan models for operatng alitude higher than 2000m(6500f) 7.Refer to derating curve. |